Description:
Device shell
Frame Type with cabin cabinet is 19 ”
Cable input From below or from above
Height 2051 or 2052 mm
Width 740/840 mm
Thickness (depth) 654/845 mm
Case color Light gray RAL 7035
Degree of protection class IP21
Ventilation system Use natural convection or internal fan temperature control module
Environment
Ambient temperature Operating from 0 to + 40 ° C
Storage temperature -40 ° C to + 70 ° C
Humidity <90% RH, no condensation
Altitude above sea level <2000 meters
AC input (for rectifier)
Input voltage 230VAC – 1 phase
Frequency 50/60 Hz
Single-phase power factor> 0.99 at 230VAC, full load
Connect 6 mm2 at each rectifier module
DC output
Nominal output voltage 24/48/110/220 VDC
Connect 10 mm2, do not connect to terminals
Adjust the voltage
<0.5% of rated output voltage
<1% within 3 seconds, 0-100 / 100
10% when changing load
Current adjustment range <1% of rated current
Current limiting range 0-100% of the rated current
Residual voltage <0.1% RMS
Main function:
Compact design, with built-in battery or extra battery.
The rectifier module compares the flexibility at the output voltage.
Control, rectify and distribute battery batteries.
Warning is displayed on the screen.
Remote alarms through warning relays.
Check and monitor the battery level to give early warning about battery battery errors.
Replace modules quickly with high flexibility and still ensure parallel operation.
Dual redundancy solution with breakers and cross-connection adjustment of two battery battery systems.
Simple, guaranteed installation and testing at the factory.