Inverter module:
Output power: 4kVA
Control: in the form of sine, control and process
Output technology: IGBT, low impedance
Remote controll:
Bottom voltage: 38.5 VDC / 86 VDC / 174 VDC
Restart at low voltage: 48 VDC / 110 VDC / 220 VDC
Over voltage: 75 VDC / 138 VDC / 276 VDC
Restart at high voltage: 72 VDC / 132 VDC / 264 VDC
Synchronization range: ± 3 Hz
Backup set:
Rated current: 120 A, 200 A
Conversion time: 3ms (converter is controlled when overloaded, low voltage, …); 20ms (controller off); 100ms (system shutdown)
Manual backup switch:
Type: contactor
Conversion time: <20ms
Electrical connection:
DC input: Connection screw at power connection bridge
AC output: Screw connection at power connection bridge
AC input (backup line): Screw connection at electrical connection bridge
Alarm: disconnected at bridge, 4 mm2
AC output:
Output voltage: 230VAC ± 5%
Frequency: 50/60 Hz
Power factor: 0.8
Peak coefficient:> 2.5
Overload protection:> 125% 12 seconds,> 150% 3 seconds.
Approx. 85% efficiency
Other See the table
Environmental conditions
Ambient temperature: operating -5 to +40 ° C, storage -40 to +70 ° C
Humidity: <90% RH, no condensation
Altitude above sea level: <2000 m
Display mode:
Control panel: showing control status and warning status
Drive module: displays output power via LED indicator
External alarm signal: check for ground connections
Remote communication: standard RS232 interface
Device shell
Type: 19 “standard stand with combined frame and swing
Cable entrance: from bottom to top or down
Dimensions (h / w / d): 2100 mm / 840 mm / 654 mm
Cabinet color: light gray RAL 7035
IP shell protection level: IP21
Ventilation: Fan control in inverter modules or in backup sets, if no natural convection is used
Standard
Safety: EN 50178
Electrochemical isolation: 3.75 kV DC
Calculating EMC radiation: EN 61000-6-3 / 4
EMC immunity: EN 61000-6-2
Enclosure protection level: EN 60529