DESCRIPTION:
Device shell
Cabin cabinet type
Cable input From below or above
Dimensions F27 (h / w / d) 1360/600/600 mm (mounted in brackets, fixed price)
Size F41 (h / w / d) Frame 2000/600/480 mm
Dimension F39 (h / w / d) 2100/840/654 mm (mounted in door frame)
Case color Light gray RAL 7035
Degree of protection class IP21
Ventilation system Use natural convection or internal fan temperature control module
Environmental conditions
Ambient temperature Operating from 0 to + 40 ° C
Storage temperature -40 ° C to + 70 ° C
Humidity <90% RH, no condensation
Altitude below sea level <2000 meters, may be larger or smaller
AC input
Input voltage 3 × 380 / 415VAC, ± 10%
Frequency 45/65 Hz
Single-phase power factor> 0.97 at 230VAC, full load
DC output
Nominal voltage 110/125/220/440 VDC
Adjust the voltage
<0.5% of nominal voltage and <1% within 3 seconds,
0-100 / 100 -10% when changing load
Adjust current <1% of rated current
Current limiting range 0-100% of the rated current
Residual voltage <0.2% RMS
92% efficiency
PRX3 SPECIFICATIONS
Input: 3x400VAC 50-60Hz
Output: 110/220 / 440VDC
Type of equipment – under-deck cabin
Display messages: output voltage, output current, temperature, low insulation resistance, error message
Warning: low voltage, high voltage, ground fault (fault of earth leakage), battery circuit error, unbalanced battery, battery temperature, rectifier error and power supply error.
Output warning: four functions of non-relay relay